Distinguish the operating spillage test from the flue-flow check, and follow the appliance’s test conditions.
A spillage test checks whether an operating open-flued appliance clears its combustion products through the flue instead of releasing them into the room. It follows a satisfactory flue-flow check; the two tests answer different questions.
Use the appliance’s prescribed method and the applicable procedure. The heat setting, warm-up period, smoke position and any permitted repeat are specific to that test. A generic five-minute wait or an improvised smoke position can give a misleading result.
- Confirm the flue and air supply are suitable and that the preceding checks are satisfactory.
- Set the appliance and room conditions as required. Leave permanent ventilation unobstructed.
- Run the appliance at the specified setting for the prescribed period, then observe smoke at the specified test point.
- Test the relevant combinations of extract fans, other equipment and internal doors to find the conditions that most adversely affect the appliance. Fans in adjoining rooms can matter too.
- Judge the smoke behaviour against the procedure. Use only its permitted repeat or additional warm-up; do not keep extending the test until a failure appears to pass.
- Record the conditions and result. If the test fails, make the appliance safe under the unsafe-situations procedure, investigate and rectify the cause, then repeat the required checks.
A draught diverter moderates the effect of flue draught on the burner; it does not make spillage harmless. A blocked flue, insufficient air or fan-induced depressurisation can prevent safe removal of products. Do not leave a failed appliance in use.